Turning Off Fire Alarm
Sounding
You can turn off Fire alarm sounding by pressing the OFF key on any keypad or
other arming/disarming device. To clear the "memory of alarm" and to reset the
detector’s alarm, enter the security code plus OFF again.
COMPATIBLE 2-WIRE SMOKE DETECTORS
System Sensor
Detector Type Model No.
Photoelectric w/heat sensor,
direct wire 2300TB
Photoelectric, direct wire 2400
Photoelectric w/heat sensor,
direct wire 2400TH
Photoelectric 2451 w/B401B base
Photoelectric w/heat sensor 2451TH w/B401B base
Ionization, direct wire 1400
System Sensor
Detector Type Model No.
Ionization 1451 w/B401B base
Photoelectric duct detector 2451 w/DH400 base
Ionization duct detect 1451DH
w/DH400 base
Low-profile, Photoelectric,
w/135°F thermal 2100T
Low-profile, Ionization type,
direct wire 1100
2000 OHMS
EOLR
ZONE 1
SMOKE
+
2-WIRE SMOKE
DETECTOR
8
9
UL NOTE:
IN UL INSTALLATIONS, ONLY ZONE 1
MAY BE USED FOR FIRE.
Figure 8. 2-Wire Smoke Detector Connected to Zone 1
Wiring 4-Wire Smoke/Combustion Detectors on Zones 2–7
The system will support as many 4-wire detectors as can be powered from
Auxiliary Power on the control, on zones 2–7. Refer to the detector’s
instructions for complete details regarding its proper installation and
operation.
1. Connect 12 volt power for the detectors from Auxiliary Power terminals 4
and 5, (which will interrupt power for fire alarm reset). Observe proper
polarity when connecting detectors.
2. Connect detectors (including heat detectors, if used) across terminals of
the zone selected (zones 2–7 may be used). All detectors must be wired in
parallel.
Remove 2000 ohm EOL resistor if connected across the selected zone
terminals. You must connect the EOL resistor across the loop wires at the last
detector.
3. To supervise power, we recommend the use of a System Sensor
No. A77-716B supervisory module.
AUX PWR
OUTPUT
TERMINALS
+
-
TO HI SIDE OF
SELECTED
ZONE
TO LO SIDE
OF SELECTED
ZONE
+
-
-
+
-
+
EOL
POWER
SUPERVISION
RELAY
MODULE
A77-716B
5
4
4-WIRE SMOKE
OR COMBUSTION
DETECTORS
2000
OHMS
EOLR
HEAT
DETECTOR
HEAT
DETECTOR
ZONES 2–7
*
+
REDBLK
VIOLET
* IF PROGRAMMED FOR FIRE
Figure 9. 4-wire Smoke Detector Connections (Zones 2–7)